| Plan Review Notes For Permit 03041473 |
| Permit Number |
03041473 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-05-16 00:00:00 | *********CORRECTIONS********* | | | | | | 1.)A NOTICE OF COMMENCEMENT MUST BE | | | FILED WITH THE CLERK OF COURTS BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2.)IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY.THE PLANS MUST BE STAMPED | | | AND THE RECEIPT ATTACHED TO THE | | | APPLICATION.233-5025 | | | | | | 3.)PROVIDE A SOILS INVESTIGATION | | | REPORT. | | | | | | 4.)WINDOW V SHOULD BE TEMPERED; CHANGE | | | THE FLOOR PLAN A6 AND THE WINDOW | | | SCHEDULE FBC 2405.2. | | | | | | 5.)'REPAIR MASONRY GAPS" AND "WINDOW | | | & SGD' DETAILS, A12, TO COMPLY WITH | | | 1707.4.4.2. | | | | | | 6.)WOOD BALCONY RAILING TO COMPLY | | | WITH FBC 1015.3. | | | | | | 7.)PROVIDE A STRUCTURAL PLAN FOR THE | | | STAIRS INDICATING HOW STAIRS AND LANDING | | | WILL BE SUPPORTED.PROVIDE A SECTION | | | FOR THE STAIRS SHOWING LOCATION AND | | | MATERIALS USED FOR FIREBLOCKING | | | FBC 2305.1.4. | | | | | | 8.)THE UPLIFT VALUES FOR SOME OF THE | | | CONNECTORS ARE INCORRECT.REFER TO | | | USP 2003 CATALOG. | | | | | | 9.)THE SINGLE HUNG WINDOW AND TILE | | | SPECS ARE ILLEGIBLE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | SAMANTHA THYNG, BUILDING PLANS EXAMINER | | | [email protected] |
|