Plan Review Notes
Plan Review Notes For Permit 03041464
Permit Number 03041464
Review Stop E
Sequence Number 6
Notes
Date Text
2004-04-17 00:00:00*********** UNSAT **************
  
 1)NOTE: PLEASE SEE SOMES NOTES FROM TWO
 PREVIOUS REVIEWS.
 A NOTICE WAS GIVEN PER FS 553.80(2)(B)
 FOR ANY OF THE SAME COMMETS 3 OR MORE
 TIMES, A 4X FEE SHALL BE ACCESSED.
 PLEASE SEE BZ#240060 ATTACHED. ARCH
 OF RECORD PER FS IS RESPONSIBLE FOR
 THE FEE. $4,380.00
 PLEASE SEE THE FOLLOWING COMMENTS FOR
 CORRECTIONS TO BE MADE TO PLANS FOR
 CODE COMPLIANCE AND CORRECTIONS REQ'D
 UNDER FS 481.219,481.221/ FAC 61G1-16.00
 -4.
  
 2)NOTE: PLEASE HAVE PLANS REPRINTED
 WITH ALL REVISIONS. PLANS ARE TO BE
 CLEAR AND VISABLE WITH ALL CHANGES.
 HAND WRITTEN/PENCIL/PEN CHANGES ON
 PLANS ARE NOT PERMITTED.
 PLANS ARE COPIES OF ORIG SIGNED AND
 SEALED PLANS WITH NEW SEAL OVER THEM?
 THIS IS A DIRECT VIOLATION OF FS.481.221
 ETC.
 PLEASE ALSO SEE FS 481.219, A CERTIFI-
 -CATE OF AUTHORIZATION # IS REQ'D FOR
 TITLE BLOCK SHOWN.
 PLEASE NOTE: IF CORRECTIONS ARE NOT
 MADE , AN ADDTIONAL 4X FEE WILL BE ADDED
 AND PLANS WILL BE TURNED INTO THE STATE
 DPBR FOR REVIEW.
  
 3)NOTE: PLEASE SEE 210.52C2 FOR REQ'D
 RECEPT FOR ISLAND. PLEASE SEE THEY ARE
 DRAWN IN ON SIGNED AND SEALED PLANS.
 NOT PERMITTED.
  
 4)NOTE: PLEASE CORRELATE RISER AND PANEL
 SCHEDULE. PANEL "B" HAS A BRKR FEED TO
 NEW POOL PANEL, YET RISER NOTES NEW
 FUSE PNL FOR POOL?? PLEASE CLARIFY.
  
 5)NOTE: PLEASE SEE 250.66 FOR SIZING
 OF GROUNDING ELECTRODE. THIS IS SHOWN
 AS A 400A SERVICE. 310.15B6, PLACES
 MIN SEC'S AS 400MCM, 400MCM ON TABLE
 250.66, INDICATES A 1/0. PLEASE ADJUST
 230.42B
 6)NOTE: PLEASE ALSO INCLUDE FOOTER STEEL
 AS PART OF THE GROUNDING ELECTRODE
 SYSTEM AS REQ'D PER 250.50
 FOOTER STEEL IS NOT SHOWN ON RISER??
  
 7)NOTE: PLEASE SEE 220.3B4 FOR LOADS
 TO BE FIGURED FOR RECESSED LTS.
 PLEASE RE-CONFIGURE AND ADJUST LOAD
 CALCULATIONS.
  
 8)NOTE: PLEASE SEE 210.12 FOR REQ'D
 ARC FAULT PROTECTION, THIS SHOULD BE
 NOTED, AND/OR LISTED ON PANEL SCHEDULE.
  
 9)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
  
 10)NOTE: PLEASE SEE 250.122 FOR SIZING
 OF EQUIPMENT GROUNDING CONDUCTOR FROM
 PANEL "B" TO POOL PANEL WITH A 80A OCP
 FEED. #10 IS NOT PERMITTED.
  
 11)NOTE: PLEASE SEE 220 FOR LOADING
 OF 80A BRKR FOR POOL PANEL. AS SHOWN
 LOAD IS EXCEEDING 80% RATING OF BRKR.??
 230.4
 PLEASE SEE LOAD CALCS IN 220
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717