| 2004-04-17 00:00:00 | *********** UNSAT ************** |
| | |
| | 1)NOTE: PLEASE SEE SOMES NOTES FROM TWO |
| | PREVIOUS REVIEWS. |
| | A NOTICE WAS GIVEN PER FS 553.80(2)(B) |
| | FOR ANY OF THE SAME COMMETS 3 OR MORE |
| | TIMES, A 4X FEE SHALL BE ACCESSED. |
| | PLEASE SEE BZ#240060 ATTACHED. ARCH |
| | OF RECORD PER FS IS RESPONSIBLE FOR |
| | THE FEE. $4,380.00 |
| | PLEASE SEE THE FOLLOWING COMMENTS FOR |
| | CORRECTIONS TO BE MADE TO PLANS FOR |
| | CODE COMPLIANCE AND CORRECTIONS REQ'D |
| | UNDER FS 481.219,481.221/ FAC 61G1-16.00 |
| | -4. |
| | |
| | 2)NOTE: PLEASE HAVE PLANS REPRINTED |
| | WITH ALL REVISIONS. PLANS ARE TO BE |
| | CLEAR AND VISABLE WITH ALL CHANGES. |
| | HAND WRITTEN/PENCIL/PEN CHANGES ON |
| | PLANS ARE NOT PERMITTED. |
| | PLANS ARE COPIES OF ORIG SIGNED AND |
| | SEALED PLANS WITH NEW SEAL OVER THEM? |
| | THIS IS A DIRECT VIOLATION OF FS.481.221 |
| | ETC. |
| | PLEASE ALSO SEE FS 481.219, A CERTIFI- |
| | -CATE OF AUTHORIZATION # IS REQ'D FOR |
| | TITLE BLOCK SHOWN. |
| | PLEASE NOTE: IF CORRECTIONS ARE NOT |
| | MADE , AN ADDTIONAL 4X FEE WILL BE ADDED |
| | AND PLANS WILL BE TURNED INTO THE STATE |
| | DPBR FOR REVIEW. |
| | |
| | 3)NOTE: PLEASE SEE 210.52C2 FOR REQ'D |
| | RECEPT FOR ISLAND. PLEASE SEE THEY ARE |
| | DRAWN IN ON SIGNED AND SEALED PLANS. |
| | NOT PERMITTED. |
| | |
| | 4)NOTE: PLEASE CORRELATE RISER AND PANEL |
| | SCHEDULE. PANEL "B" HAS A BRKR FEED TO |
| | NEW POOL PANEL, YET RISER NOTES NEW |
| | FUSE PNL FOR POOL?? PLEASE CLARIFY. |
| | |
| | 5)NOTE: PLEASE SEE 250.66 FOR SIZING |
| | OF GROUNDING ELECTRODE. THIS IS SHOWN |
| | AS A 400A SERVICE. 310.15B6, PLACES |
| | MIN SEC'S AS 400MCM, 400MCM ON TABLE |
| | 250.66, INDICATES A 1/0. PLEASE ADJUST |
| | 230.42B |
| | 6)NOTE: PLEASE ALSO INCLUDE FOOTER STEEL |
| | AS PART OF THE GROUNDING ELECTRODE |
| | SYSTEM AS REQ'D PER 250.50 |
| | FOOTER STEEL IS NOT SHOWN ON RISER?? |
| | |
| | 7)NOTE: PLEASE SEE 220.3B4 FOR LOADS |
| | TO BE FIGURED FOR RECESSED LTS. |
| | PLEASE RE-CONFIGURE AND ADJUST LOAD |
| | CALCULATIONS. |
| | |
| | 8)NOTE: PLEASE SEE 210.12 FOR REQ'D |
| | ARC FAULT PROTECTION, THIS SHOULD BE |
| | NOTED, AND/OR LISTED ON PANEL SCHEDULE. |
| | |
| | 9)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | |
| | 10)NOTE: PLEASE SEE 250.122 FOR SIZING |
| | OF EQUIPMENT GROUNDING CONDUCTOR FROM |
| | PANEL "B" TO POOL PANEL WITH A 80A OCP |
| | FEED. #10 IS NOT PERMITTED. |
| | |
| | 11)NOTE: PLEASE SEE 220 FOR LOADING |
| | OF 80A BRKR FOR POOL PANEL. AS SHOWN |
| | LOAD IS EXCEEDING 80% RATING OF BRKR.?? |
| | 230.4 |
| | PLEASE SEE LOAD CALCS IN 220 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |