| Plan Review Notes For Permit 03041464 |
| Permit Number |
03041464 |
|
| Review Stop |
E |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2004-03-12 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} SEE NOTE #2 FROM PREVIOUS REVIEW. | | | " ANY CHANGES MADE TO PLANS THAT WERE | | | DRAWN BY A DESIGN PROFESSIONAL MUST BE | | | MADE BY THE DESIGNER OF RECORD PER | | | 61G1-16.003 FAC." | | | | | | 2} NOTE #6 FROM PREVIOUS REVIEW: SUBMIT | | | A PANEL SCHEDULE FOR "C". NOW BEING | | | CALLED "POOL PANEL". | | | | | | 3} PLEASE NOTE THAT THE 20K CALCULATION | | | SHOWN ON PANEL "B" FOR THE POOL PANEL | | | EXCEEDS 80 AMPS, WHICH IS SHOWN AS THE | | | MAIN FOR THAT PANEL. | | | | | | 4} LIST THE OCP RATINGS FOR ALL | | | CIRCUITS LISTED ON PANEL SCHEDULES. | | | | | | 5} INDICATE COMPLIANCE WITH 210.8(A)(6) | | | FOR THE ISLAND ON THE PLAN.(KITCHEN). | | | | | | PLEASE NOTE THAT ATTACHED IS A COPY OF | | | FL. 553.80(2)(B), BE SURE THAT THE | | | ARCHITECT IS MADE AWARE OF THIS | | | ATTACHMENT AS THIS FEE IS HIS | | | RESPONSIBILITY, AND IS MANDATORY BY | | | STATUTE. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|