| Plan Review Notes For Permit 03041464 |
| Permit Number |
03041464 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2004-01-09 00:00:00 | | | | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE NOTE, ALL PLANS DRAWN | | | BY AN ARCHITECT/ENGINEER CONTAIN- | | | -ING A TITLE BLOCK: MUST BE SIGNED, | | | DATED AND SEALD BY THAT ARCH/ENG. | | | PER FS 481.221 471.025.HAND DRAWN | | | CHANGES TO PLANS FOR PUBLIC RECORD ARE | | | NOT ACCEPTABLE. | | | | | | 2} ANY CHANGES MADE TO PLANS THAT WERE | | | DRAWN BY A DESIGN PROFESSIONAL MUST BE | | | MADE BY THE DESIGNER OF RECORD PER | | | 61GI-16.003 FAC. | | | | | | 3} PANEL "A" DOES NOT LIST THE OCP FOR | | | PANEL "C" AND THE LOAD CALC REMAINED | | | THE .AME.PLEASE CORRECT. | | | | | | 4} PLEASE NOTE THAT RECESSED LUMINAIRS | | | ARE TO BE CALCULATED PER 220.3(B)(4). | | | | | | 5} RECOMPUTE THE LOAD CALCULATIONS TO | | | REFLECT ALL REVISED LOADS. | | | | | | 6} SUBMIT A PANEL SCHEDULE FOR "C". | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] |
|