Notes
Date Text
2003-06-10 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SHT E2 SANITARY RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN, NOR DOES IT
 MEET CODE REQUIREMENTS. SOME FIXTURES
 ARE NOT SHOWN ON RISER, SOME FIXTURES
 ARE NOT VENTED, AND THE LAYOUT DOES NOT
 REFLECT THE FLOOR PLAN.
 2) PLEASE SEE ATTACHED SHEET AS AN EXAM-
 PLE OF A RISER DIAGRAM THAT MEETS CODE
 REQUIREMENTS AND REFLECTS THE FLOOR PLAN
  
 REVIEW BY KEN STEVENS