2003-06-13 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03041464
 ADD: 2330 TECUMSEH DR
 CONT: COLUMBIA BUILDING GROUP
 TEL: (561)624-9610
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DENIED
  
 1) PLANS STILL INDICATE HUGHES PRODUCT
 OR THE NAME CHANGED FROM HUGHES TO USP
 AND THE OLD MODEL NUMBER.
  
 2) META 20(2) STRAPS @ 130%= 1985 NOT
 THE 2410 INSCHEDULE
  
 3) STORM SHUTTER SCHEDULE WINDOW 2& 3
 ARE 24"X120" THE SHUTTER 15X36?????
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)805-6715