| 2003-04-28 00:00:00 | DENIED |
| | ~~~~~~ |
| | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | TO THE PLANS FOR CODE COMPLIANCE AND RES |
| | UBMIT FOR REVIEW. |
| | |
| | 1} THE GEC IS INCORRECT PER 250-66,#2CU |
| | MINIMUM. |
| | |
| | 2} THE 1/0 EQUIPMENT GROUND FROM THE |
| | METER TO THE DISCONNECTS CREATES A |
| | PARALLEL PATH TO GROUND WITH THE |
| | NEUTRAL AND MUST NOT BE INSTALLED |
| | BEFORE THE FIRST MEANS OF DISCONNECT. |
| | |
| | 3} THE OCP FOR AIR HANDLERS #1 & #3 ARE |
| | INCORRECT. |
| | |
| | 4} THE CONDUCTORS AND OCP ARE INCORRECT |
| | FOR AHU #2. |
| | |
| | 5} PLEASE LIST THE REQ'D BATH(S) |
| | CIRCUIT(S), PER 210-11-C-3 |
| | MUST BE 20A AND #12AWG, ON THE PANEL |
| | SCHEDULE. |
| | |
| | 6} PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CIRCUITS ON PANEL |
| | SCHEDULE OR NOTE ON PLANS FOR BRANCH |
| | CIRCUIT PROTECTION. PER 210-12 |
| | |
| | 7} ALL LIGHTING FOR CLOSETS MUST COMPLY |
| | WITH 410-8, NOTE LIGHTS DRAWN OVER |
| | SHELVING. |
| | |
| | 8} ALL ELECTRICAL PANELS,DISCONNECT AND |
| | EQUIPMENT MUST COMPLY WITH 110-26. |
| | |
| | 9} PLEASE NOTE KITCHEN COUNTER- |
| | -SPACE RECEPT SPACING SHALL MEET ART; |
| | 210-52C 1,2,3,4,AND 5. |
| | |
| | 10} PLEASE IDENTIFY ALL AREAS AND ROOMS |
| | ON THE ELECTRICAL SHEETS. |
| | |
| | THE ARCHITECTURAL & ELECTRICAL DRAWINGS |
| | DO NOT CORRESPOND IN SOME AREAS. NOTE |
| | THE BATH/HALLWAY WALL OFF BED ROOM #2. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/805-6718 |