Plan Review Notes
Plan Review Notes For Permit 03041464
Permit Number 03041464
Review Stop E
Sequence Number 1
Notes
Date Text
2003-04-28 00:00:00DENIED
 ~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 TO THE PLANS FOR CODE COMPLIANCE AND RES
 UBMIT FOR REVIEW.
  
 1} THE GEC IS INCORRECT PER 250-66,#2CU
 MINIMUM.
  
 2} THE 1/0 EQUIPMENT GROUND FROM THE
 METER TO THE DISCONNECTS CREATES A
 PARALLEL PATH TO GROUND WITH THE
 NEUTRAL AND MUST NOT BE INSTALLED
 BEFORE THE FIRST MEANS OF DISCONNECT.
  
 3} THE OCP FOR AIR HANDLERS #1 & #3 ARE
 INCORRECT.
  
 4} THE CONDUCTORS AND OCP ARE INCORRECT
 FOR AHU #2.
  
 5} PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S), PER 210-11-C-3
 MUST BE 20A AND #12AWG, ON THE PANEL
 SCHEDULE.
  
 6} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 7} ALL LIGHTING FOR CLOSETS MUST COMPLY
 WITH 410-8, NOTE LIGHTS DRAWN OVER
 SHELVING.
  
 8} ALL ELECTRICAL PANELS,DISCONNECT AND
 EQUIPMENT MUST COMPLY WITH 110-26.
  
 9} PLEASE NOTE KITCHEN COUNTER-
 -SPACE RECEPT SPACING SHALL MEET ART;
 210-52C 1,2,3,4,AND 5.
  
 10} PLEASE IDENTIFY ALL AREAS AND ROOMS
 ON THE ELECTRICAL SHEETS.
  
 THE ARCHITECTURAL & ELECTRICAL DRAWINGS
 DO NOT CORRESPOND IN SOME AREAS. NOTE
 THE BATH/HALLWAY WALL OFF BED ROOM #2.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718