2003-10-21 00:00:00ENGINEER'S REVISIONS DATED 9/11/03 SK4
 & SK5.
  
 SK4 HAS ILLEGIBLE TYPE.
  
 PLEASE PROVIDE A SITE/KEY PLAN SHOWING
 THE LOCATION OF THE PROPOSED METER
 CLOSET.
  
 SHOW A PLAN VIEW WITH DIMENSIONS FOR
 THE WIDTH/SIZE OF THE STRUCTURE, INCLUDE
 THE WORKING CLEARANCES IN ACCORDANCE
 WITH
 THE NEC, AND OTHER PERTINENT
 INFORMATION LIKE ACCESS DOORS.
  
 THE DELEGATED ENGINEERING NOTES FOR THE
 METAL STUD WALL HAS LITTLE DESIGN
 INFORMATION SUCH AS NATURE, LOCATION
 AND MAGNITUDE OF FORCES TO BE RESISTED.
 THERE IS NO INFORMATION FOR THE WOOD
 TRUSSES.SEE CHAPTER 61-G15-30 OF THE
 FL ADMINISTRATIVE CODE.
  
 WHAT WILL THE ROOF BE SHEATHED WITH?
  
 SHOW THE TERMITE PROTECTION
 REQUIREMENTS AS PROVIDED FOR IN FBC
 1816.1.6.