| Plan Review Notes For Permit 03041303 |
| Permit Number |
03041303 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-05-23 00:00:00 | DENIED | | | REFERENCE: FBC-2001 424.2 SWIMMING POOLS | | | FLA STATUTES | | | | | | A) PREVIOUS REVIEW COMMENTS NOT ADDRESS- | | | ED. | | | 1) PIPING SCHEMATIC AND POOL LAYOUT DO | | | NOT MATCH. NO VACUUM LINE SHOWN ON | | | PIPING SCHEMATIC. | | | 2) 61G15-23.002(1) THE DATE THAT THE | | | PLAN IS SIGNED AND SEALED SHALL BE | | | ENTERED ON PLANS. | | | 3) FBC-2001 424.2.14.4 CONNECTIONS, ALL | | | WATER HEATING EQUIPMENT SHALL BE INSTAL- | | | LED WITH FLANGES OR UNION CONNECTIONS | | | ADJACENT TO THE HEATER. (ADD TO NOTES) | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 | | | (561) 805-6721 | | | FAX (561) 653-2692 |
|