| Plan Review Notes For Permit 03041300 |
| Permit Number |
03041300 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-05-12 00:00:00 | DENIED: | | | | | | 1.PLAN SHEET AC-1 SEEMS TO INDICATE | | | THE CONDENSATE TERMINATING INTO THE | | | FLOOR DRAIN OF THE MECHANICAL ROOM. | | | AS PER CITY CODE SEC 90-125 - | | | PROHIBITIONS & LIMITATIONS OF DISCHARGE | | | SUB-SECTION (B)(5).CONDENSATE SHALL | | | NOT TERMINATE INTO SANITARY. | | | | | | 2.MECHANICAL PLANS DO NOT INDICATE ANY | | | OF THE EXHAUST FANS BEING TIED TO | | | EMERGENCY POWER.PLEASE CLARIFY. | | | | | | 3.2001 FBC(M) 510.8, DUCTS UTILIZED TO | | | CONVEY HAZARDOUS EXHAUST SHALL BE | | | CONSTRUCTED OF G90 GALVANIZED, WITH A | | | MINIMUM NOMINAL THICKNESS AS SPECIFIED | | | IN TABLE 510.8. | | | | | | SEE ALSO COMMENTS FOR BUILDING AND FIRE | | | DEPARTMENT. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|