Plan Review Notes
Plan Review Notes For Permit 03041300
Permit Number 03041300
Review Stop B
Sequence Number 1
Notes
Date Text
2003-05-05 00:00:00PLAN REVIEW ONLY NOT A PERMIT
 APPLICATION.
  
 THE PROPOSED BUILDING AREA 9.9 KSF
 EXCEEDS THE ALLOWBLE AREA IN FBC TABLE
 500 FOR TYPE IV CONSTRUCTION, 5.0 KSF.
 THE MINIMUM CONSTRUCTION TYPE IS TYPE
 II FS.
  
 THE MEZZANINE AS SHOWN DOES NOT COMPLY
 WITH THE EGRESS REQUIREMENTS OF FBC
 1005.7 FOR A SINGLE MEANS OF EGRESS IN
 AN GROUP H OCCUPANCY.
  
 AT TIME OF PERMIT APPLICATION AN
 ESTIMATE OF THE TYPE AND QUANTITIES OF
 MATERIALS STORED IN THE BUILDING WILL
 BE NECESSARY.SEE FBC 308.2.3 AND FBC
 308.2.4.
  
 THE PERMIT PLANS MUST SHOW THE SPILL
 CONTROL AND CONTAINMENT METHODS IN
 ACCORDANCE WITH FBC 407.2.3. AND THE
 STANDBY POWERAS PROVIDED FOR IN FBC
 407.2.9.4.