Plan Review Notes
Plan Review Notes For Permit 03041294
Permit Number 03041294
Review Stop B
Sequence Number 1
Notes
Date Text
2003-05-15 00:00:00CHECKLIST:
 1-SURVEY DOESN'T MATCH FLOOR PLANS
 SUBMITTED. SURVEY IS FOR MODEL 202,
 WHILE PLANS ARE FOR MODEL 203.
 2-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS WITH UPDATED SBCCI REPORT.
 3-REVISE DETAIL S21 FOR COLUMN LOCATED
 BETWEEN GARAGE AND STAIRWAY TO MATCH
 CONDITIONS SHOWN ON 2ND FLOOR FRAMING
 PLAN. SECTION 104.2.1.2 OF CITY
 AMENDMENTS TO FBC 2001.
 4-WINDOW 34SH DOESN'T PROVIDE THE 24"
 CLEAR HEIGHT REQUIRED BY SEC. 1005.4
 FBC 2001 FOR BEDROOMS. REVISE AS
 REQUIRED.
 5-ROOF FRAMING PLAN. REVISE CONNECTOR
 TC-1 SPECIFIED FOR FRAMED WALL. NEED
 WOOD TO WOOD CONNECTOR. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.