| Plan Review Notes For Permit 03041294 |
| Permit Number |
03041294 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-05-15 00:00:00 | CHECKLIST: | | | 1-SURVEY DOESN'T MATCH FLOOR PLANS | | | SUBMITTED. SURVEY IS FOR MODEL 202, | | | WHILE PLANS ARE FOR MODEL 203. | | | 2-PROVIDE COMPLETE INFORMATION FOR STORM | | | SHUTTERS WITH UPDATED SBCCI REPORT. | | | 3-REVISE DETAIL S21 FOR COLUMN LOCATED | | | BETWEEN GARAGE AND STAIRWAY TO MATCH | | | CONDITIONS SHOWN ON 2ND FLOOR FRAMING | | | PLAN. SECTION 104.2.1.2 OF CITY | | | AMENDMENTS TO FBC 2001. | | | 4-WINDOW 34SH DOESN'T PROVIDE THE 24" | | | CLEAR HEIGHT REQUIRED BY SEC. 1005.4 | | | FBC 2001 FOR BEDROOMS. REVISE AS | | | REQUIRED. | | | 5-ROOF FRAMING PLAN. REVISE CONNECTOR | | | TC-1 SPECIFIED FOR FRAMED WALL. NEED | | | WOOD TO WOOD CONNECTOR. SECTION | | | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
|