| 2003-05-10 00:00:00 | *****CORRECTIONS****** |
| | |
| | 1.)SEPARATE PERMITS REQUIRED |
| | (MECHANICAL). |
| | |
| | 2.)PROVIDE AREA CALCULATIONS ON THE |
| | PLAN. |
| | |
| | 3.)IMPACT FEES ARE REQUIRED TO BE |
| | PAID AND THE PLANS STAMPED BEFORE THE |
| | PERMIT CAN BE ISSUED.CALL 233-5025 |
| | FOR MORE INFORMATION. |
| | |
| | 4.)ENERGY CALCS REQUIRED FBC13-101.2. |
| | |
| | 5.)PLANS WITH AN ENGINEER'S TITLE |
| | BLOCK ARE REQUIRED TO BE SEALED, SIGNED |
| | AND DATED BY THE ENGINEER. |
| | |
| | 6.)PLAN SHOWS AN 8' GARAGE DOOR, |
| | PRODUCT APPROVALS ARE FOR 16'.SUBMIT |
| | NEW PRODUCT APPROVALS. |
| | |
| | 7.)PLANS REFER TO PRODUCT APPROVAL |
| | NUMBERS WHICH APPEAR TO BE EXPIRED AND |
| | WERE NOT PROVIDED WITH THE PLAN. |
| | |
| | 8.)BUCKS TO PROVIDE FULL SUPPORT, |
| | REFER TO TYP WINDOW & SGD DETAIL, FBC |
| | 1707.4.4.2. |
| | |
| | 9.)USP CONNECTOR UPLIFT VALUES HAVE |
| | BEEN REVISED.REFER TO 2003 CATALOG. |
| | |
| | 10.)FIRESTOP REQUIRED, FBC 705.3 (NEW |
| | INT WALL SECTION). |
| | |
| | 11.)PROVIDE A DETAIL FOR THE NEW |
| | EXTERIOR WALL. |
| | |
| | 12.)PROVIDE PRODUCT APPROVALS FOR THE |
| | ARCHED WINDOW AND THE LOUVERED VENT. |
| | |
| | 13.)TWO DIFFERENT DOOR SPECS WERE |
| | PROVIDED.WHICH IS BEING USED AS THE |
| | EXTERIOR DOOR NEXT TO THE NEW GARAGE |
| | DOOR?PRODUCT APPROVALS ARE NOT |
| | REQUIRED FOR INTERIOR DOORS. |
| | |
| | 14.)TWO DIFFERENT WINDOW PRODUCT |
| | APPROVALS WERE SUBMITTED.NEITHER WERE |
| | FOR AN ARCHED WINDOW. |
| | |
| | 15.)WHEN SUBMITTING PRODUCT APPROVALS, |
| | BE SURE THAT THEY ARE LEGIBLE. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | SAMANTHA THYNG, BUILDING PLANS EXAMINER |
| | [email protected] |