2004-02-24 00:00:00PROVISO:
 PLANS SUBMITTED AS A RESTAMP.WHEN
 COMPARED TO PLANS ON FILE WITH THE CITY
 OF WEST PALM BEACH, THERE HAVE BEEN
 REVISIONS MADE TO THE PLANS SUBMITTED
 AS "RESTAMP".REVISION FEES TO BE
 ACCESSED.
  
 1.PLAN SHEET M-3, DUCTS APPEAR TO
 PENETRATE RATED WALLS.FIRE DAMPERS
 ARE NOT SHOWN ON PLAN.PLEASE CLARIFY.
 INDICATE ON PLAN SHOULD DUCTS COMPLY
 WITH 2001 FBC(M) 607.1.3 ITEM #3, 1
 THROUGH 4.
  