| Date |
Text |
| 2003-06-30 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | |
| | 1) CALCULATIONS FOR PRIMARY AND SECOND- |
| | ARY ROOF DRAINS INSUFFICIENT. SUBMIT |
| | CALCULATIONS SHOWING SQUARE FOOTAGE FOR |
| | THE FLAT ROOF. SHOW 1/2 AREA OF ALL |
| | VERTICAL WALLS INCLUDING PARAPTES. SHOW |
| | SQUARE FOOTAGE FOR ALL ROOF AREA THAT |
| | DRAINS TO FLAT ROOF FROM ABOVE. 1106.2 |
| | 1106.4 - SECTION 1106.6 |
| | 2) SECONDARY DRAIN SHALL BE SIZED PER |
| | SEC 1107.3. THE MINIMUM CROSS-SECTIONAL |
| | AREA OF AN OVERFLOW SCUPPER SHALL BE 3 |
| | TIMES THE CROSS-SECTIONAL AREA OF THE |
| | PRIMARY ROOF DRAIN AND THE SCUPPER SHALL |
| | HAVE A MINIMUM OPENING DIMENSION OF 4" |
| | 3) SCUPPER OPENINGS SHALL BE LARGE |
| | ENOUGH FOR COMBINED AREA OF PRIMARY AND |
| | SECONDARY DRAINS, (SCUPPERS). SUBMIT A |
| | DETAIL FOR SCUPPER OPENING SHOWING WIDTH |
| | AND HEIGHT OF OPENING. SECION 104.2.1 |
| | 4) THIS IS THE THIRD REJECTION OF THIS |
| | PLAN FOR THE SAME REASON - PLEASE SEE |
| | ATTACHED SHEET CONCERNING FLORIDA STATU- |
| | TE 553.80(2)(B) |
| | 5) THE INFORMATION SUBMITTED IS THE RE- |
| | SULT OF THE CALCULATIONS, BUT NOT THE |
| | ACTUAL CALCULATIONS. |
| | ********WHEN RESUBMITTING PLANS********* |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN |
| | BE FOUND, WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |