| Plan Review Notes For Permit 03041216 |
| Permit Number |
03041216 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-06-09 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FLORIDA STATUTES | | | | | | 1) CALCULATIONS FOR PRIMARY AND SECOND- | | | ARY ROOF DRAINS SHALL SHOW TOTAL SQUARE | | | FEET BEING DRAINED. CALCULATIONS SHALL | | | SHOW 1/2 AREA OF ALL VERTICAL WALLS, | | | (1106.4), ALL AREA OF ALL ROOFS THAT | | | DRAIN TO ROOF FROM ABOVE, (1106.2). | | | SECTION 104.2.1. GUTTERS SHALL BE SIZED | | | PER TABLE 1106.6 FOR PRIMARY DRAIN ONLY. | | | 2) SECONDARY DRAIN SHALL BE SIZED PER | | | SECTION 1107.3. THE MINIMUM CROSS-SECT- | | | IONAL AREA OF AN OVERFLOW SCUPPER SHALL | | | BE THREE TIMES THE CROSS-SECTIONAL AREA | | | OF THE PRIMARY ROOF DRAIN AND THE SCUPP- | | | ER SHALL HAVE A MINIMUM OPENING DIMEN- | | | SION OF 4 INCHES. | | | 3) SCUPPER OPENINGS SHALL BE LARGE | | | ENOUGH FOR COMBINED AREA OF PRIMARY AND | | | SECONDARY DRAINS, (SCUPPERS). PLEASE | | | SUBMIT A DETAIL FOR SCUPPER OPENING, | | | SHOWING WIDTH AND HEIGHT OF OPENING. | | | SECTION 104.2.1 | | | 4) THE PERSONAL SEAL, SIGNATURE AND DATE | | | OF THE ARCHITECT SHALL APPEAR ON ALL | | | ARCHITECTURAL DOCUMENTS TO BE FILED FOR | | | PUBLIC RECORD. 61G1-16.003 | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 | | | (561) 805-6721 | | | FAX (561) 653-2692 |
|