| 2003-05-07 00:00:00 | ************* UNSAT************* |
| | |
| | 1)NOTE: PLEASE VERIFY CODE LETTER |
| | OF FIRE PUMP MOTOR/OR PLEASE NOTE AS |
| | "LISTED W/OCP SET FOR LOCKED ROTOR". |
| | 695-4-B1 |
| | |
| | 2)NOTE: PLEASE PLACE NOTE ON PLANS FOR |
| | CONTRACTOR TO PROVIDE SIGNAGE FOR MEANS |
| | OF DISC OF MAINS 1 AND FIRE PUMP/ LOCAT- |
| | -IONS ETC.230-2E |
| | |
| | 3)NOTE: PLEASE SEE THAT THERE IS A PANEL |
| | -BOARD "M" SHOWN ON SCHEDULES, BUT NOTH- |
| | ING SHOWN ON RISER DIAGRAM? SHOWN ON |
| | FLOOR PLAN ALSO? |
| | |
| | 4)NOTE: PLEASE SHOW LOAD CALCULATIONS, |
| | PLEASE ALSO SHOW ALL CONTINUOUS LOADS |
| | AT 125%. 220-3,220-10,220-11,220-13, |
| | 215-3,230-42 ETC. |
| | |
| | 5)NOTE: PLEASE CORRELATE PANEL "A" AND |
| | RISER, SHOWS FEED TO PANEL "T" W/ #2`S |
| | AND RISER SHOWS # 1`S? |
| | |
| | 6)NOTE: PLEASE SEEPANEL"A" ALSO SHOWS |
| | FEEDING PANEL "M". |
| | |
| | 7)NOTE: PLEASE SEE PANEL "L", BOXES |
| | CHECKED FOR MLO& MCB. RISER, SHOWS AS |
| | MLO. (MISPRINT) |
| | |
| | 8)NOTE: PLEASE SEE 700-16 FOR FIXTURES |
| | LOCATED IN SOME AREAS THAT ARE SHOWN |
| | W/ SINLGE BALLAST(ELEC RMS). |
| | |
| | 9)NOTE: PLEASE CLARIFY LIGHTING IN AREAS |
| | /HALLWAYS NEARS PANELS, B>L>M. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. PLEASE TAKE OUT ANY OLD/VOIDED |
| | SHEETS AND INSERT NEW SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | |
| | IF THERE ARE ANY QUESTIONS, PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |