Plan Review Notes
Plan Review Notes For Permit 03041003
Permit Number 03041003
Review Stop E
Sequence Number 1
Notes
Date Text
2003-04-25 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE REDRAW THE PLANS TO REFLECT
 COMPLIANCE WITH THE FOLLOWING CODE
 ARTICLES, AND RESUBMIT FOR REVIEW.
  
 1} PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 2} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 3} PLEASE NOTE, EITHERMISSING
 LIGHTING AND/OR CLARIFY EGRESS LIGHTING
 PER 210-70 OF THE NEC.
  
 4} PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2',6',12' RULE PER 210-52.
  
 5} PLEASE ADD SMOKE DETECTORS TO COMPLY
 WITH 8-1.4.2 NFPA-72.
  
 6} ADD OUTSIDE GFI TO COMPLY WITH
 210-52(E),IF THERE IS NONE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718