| Plan Review Notes For Permit 03041003 |
| Permit Number |
03041003 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-04-25 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE REDRAW THE PLANS TO REFLECT | | | COMPLIANCE WITH THE FOLLOWING CODE | | | ARTICLES, AND RESUBMIT FOR REVIEW. | | | | | | 1} PLEASE LIST THE REQ'D BATH(S) | | | CIRCUIT(S). PER 210-11-C-3 | | | MUST BE 20A AND #12AWG. | | | | | | 2} PLEASE LIST THE REQ'D ARC | | | FAULT PROTECTED CIRCUITS ON PANEL | | | SCHEDULE OR NOTE ON PLANS FOR BRANCH | | | CIRCUIT PROTECTION. PER 210-12 | | | | | | 3} PLEASE NOTE, EITHERMISSING | | | LIGHTING AND/OR CLARIFY EGRESS LIGHTING | | | PER 210-70 OF THE NEC. | | | | | | 4} PLEASE SHOW ALL OUTLET SPACING | | | TO MEET 2',6',12' RULE PER 210-52. | | | | | | 5} PLEASE ADD SMOKE DETECTORS TO COMPLY | | | WITH 8-1.4.2 NFPA-72. | | | | | | 6} ADD OUTSIDE GFI TO COMPLY WITH | | | 210-52(E),IF THERE IS NONE. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|