| Plan Review Notes For Permit 03040986 |
| Permit Number |
03040986 |
|
| Review Stop |
E |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2003-06-30 00:00:00 | *********** UNSAT ************** | | | | | | 1)NOTE: PLEASE CORRELATE ELECTRICAL | | | DIAGRAM WITH ALL EQUIPMENT BEING INSTALL | | | -ED. | | | PLEASE SEE PLAN, ONLY ONE PUMP SHOWN? | | | | | | PLEASE INCLUDE ALL WIRE, CONDUIT SIZES. | | | PLEASE INCLUDE LOAD CALCULATIONS WITH | | | NEW AND EXISTING LOADS AND SIZE OF | | | EXISTING SERVICE. | | | | | | PLEASE SEE LETTER ATTACHED FOR DESIGNER | | | OF RECORD. PLEASE NOTE, THIS IS REQ'D | | | UNDER FS 553.80(2)(B). | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|