| Plan Review Notes For Permit 03040986 |
| Permit Number |
03040986 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2003-06-17 00:00:00 | DENIED | | | REFERENCE: FBC-2001 424.2 SWIMMING POOLS | | | | | | 1) SECTION 424.2.6.6.3, A MINIMUM OF TWO | | | SUCTION INLETS SHALL BE PROVIDED FOR | | | EACH PUMP IN THE INLET SYSTEM, SEPARATED | | | BY A MINIMUM OF 3 FEET OR LOCATED ON TWO | | | DIFFERENT PLANES ECT. - ONLY TWO DRAIN | | | ARE SHOWN ON PLANS. MINIMUM OF 4 MAIN | | | DRAINS REQUIRED. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 | | | (561) 805-6721 | | | FAX (561) 653-2692 |
|