Plan Review Notes
Plan Review Notes For Permit 03040986
Permit Number 03040986
Review Stop P
Sequence Number 3
Notes
Date Text
2003-06-17 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 1) SECTION 424.2.6.6.3, A MINIMUM OF TWO
 SUCTION INLETS SHALL BE PROVIDED FOR
 EACH PUMP IN THE INLET SYSTEM, SEPARATED
 BY A MINIMUM OF 3 FEET OR LOCATED ON TWO
 DIFFERENT PLANES ECT. - ONLY TWO DRAIN
 ARE SHOWN ON PLANS. MINIMUM OF 4 MAIN
 DRAINS REQUIRED.
  