| Plan Review Notes For Permit 03040935 |
| Permit Number |
03040935 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-06-05 00:00:00 | PROVISO | | | ~~~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE NOTE THE LIGHTS IN THE DINING | | | AREA CANNOT BE ON THE SMALL APPLIANCE | | | CIRCUIT PER 210-52(B)(2).PLEASE PUT ON | | | ANOTHER CIRCUIT AND LIST ON PANEL | | | SCHEDULE. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|