| 2003-05-07 00:00:00 | ***************** UNSAT **************** |
| | |
| | PLEASE SEE CHAPTER 34 OF THE FBC FOR |
| | ADDITIONS AND REMODELS.3401.7 |
| | PLEASE SHOW ALL EXISTING ELECTRICAL AS' |
| | IT WOULD NEED TO MEET NEC. SD`S, DEVICES |
| | ETC. 210-52/210-12, NFAP-72 8-1.4.2 |
| | PLEASE NOTE THERE ARE SOME ITEMS ON |
| | PANEL SCHEDULES FOR EXSITING,THAT DO NOT |
| | CLARIFY IF SOME EXISTING MEET NEC, |
| | PLEASE SEE THE FOLLOWING NOTES. |
| | |
| | 1)NOTE: PLEASE LIST THE REQ`D EXIST/NEW |
| | SMALL APPLIANCE CIRCUITS 210-11-C-1 |
| | ETC. |
| | |
| | 2)NOTE: PLEASE LIST THE REQ`D BATH CIR- |
| | -CUIT(S) PER 210-52D/210-11-C-3 |
| | SHOWN ON LAUNDRY CIRCUIT. |
| | MUST BE DEDICATED. |
| | |
| | 3)NOTE: PLEASE REMOVE LAUNDRY FROM BATH |
| | CIRCUIT. REQ`D TO BE DEDICATED ALSO PER |
| | 210-11-C2/ 220-16 |
| | |
| | 4)NOTE: PLEASE SEE 210-52 FOR RECEPT |
| | SPACING ALONG WALLS. |
| | |
| | 5)NOTE: PLEASE SEE THAT ALL OUTLETS |
| | SERVING KITCHEN COUNTERSPACE. 210-8A-6 |
| | SHOWS NEW RECEPT ON COUNTER ON CIRCUIT |
| | W/ OUTSIDE GFI? |
| | |
| | 6)NOTE: PLEASE SIZE GROUNDING ELECTRODE |
| | PER 250-66. |
| | |
| | 7)NOTE: PLEASE SHOW GROUNDING AT DETACH- |
| | -ED BLDG.250-31 BOND TO NEW FOOTER ALSO. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. PLEAS TAKE OUT ANY OLD/VOIDED |
| | SHEETS AND INSERT NEW SHEETS INTO TWO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | IF THERE ARE ANY QUESTIONS, PLEASE CALL. |
| | |