| 2003-05-16 00:00:00 | *******CORRECTIONS******* |
| | SAMANTHA THYNG, BUILDING PLANS EXAMINER |
| | [email protected]. |
| | |
| | 1.)SEPARATE PERMITS REQUIRED. |
| | |
| | 2.)BEFORE A PERMIT CAN BE ISSUED, A |
| | NOTICE OF COMMENCEMENT MUST BE FILED |
| | WITH THE CLERK OF COURTS. |
| | |
| | 3.)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY.THE PLANS MUST BE STAMPED |
| | AND THE RECEIPT ATTACHED TO THE |
| | APPLICATION.233-5025. |
| | |
| | 4.)DETAIL 3, A-6 SHOWS THE ROOF AS A |
| | FLAT DECK WITH TILE.REVISE.GIVE |
| | CONNECTIONS WITH UPLIFT. |
| | |
| | 5.)THE TWO ADDITIONS DO NOT COMPLY |
| | WITH TABLE 600.REVISE, AND PROVIDE |
| | CALCULATIONS TO SHOW HOW THE ADDITIONS |
| | WILL BE IN COMPLIANCE. |
| | |
| | 6.)SECTION 3, A-6, DOES NOT SHOW |
| | ATTACHMENTS. |
| | |
| | 7.)PROVIDE A DETAIL FOR THE WOOD WALL |
| | SHOWN ON THE FLOOR PLAN, WITH ALL |
| | ATTACHMENTS. |
| | |
| | 8.)ENERGY CALCS ARE FOR 965 SQUARE |
| | FEET.WHAT IS THIS FOR?PROVIDE ENERGY |
| | CALCS FOR THE TWO ADDITIONS, ONE FOR |
| | EACH, WITH THE CORRECT SQUARE FOOTAGE. |
| | |
| | 9.)THE ROOF SHEATHING SCHEDULE ON S1 |
| | CONFLICTS WITH S3. |
| | |
| | 10.) SPECIFY ATTACHMENTS WITH UPLIFT |
| | ON THE ROOF FRAMING PLAN. |
| | |
| | 11.)THE PLAN SHOWS A PICTURE OF A |
| | SINGLE HUNG EGRESS WINDOW, BUT THE WORDS |
| | CALL THIS WINDOW A CASEMENT.EGRESS |
| | WINDOWS ARE NOT REQUIRED DUE TO |
| | THE BEDROOM HAVING ANOTHER MEANS OF |
| | EGRESS (DOOR TO THE OUTSIDE). |
| | |
| | 12.)W104 SHOWS A DOOR; SHOULD THIS |
| | BE SIDELITES? |
| | |
| | 13.)ATTIC ACCESS REQUIRED FBC2309. |
| | |
| | 14.)HOW WILL THE ADDITION TIE INTO |
| | THE EXISTING BUILDING? |
| | |
| | 15.)FIRESTOP REQUIRED FBC 705.3. |
| | |
| | 16.)SOFFIT VENTS REQUIRED, FBC 2309.7. |
| | PROVIDE CALCULATIONS TO SHOW |
| | COMPLIANCE. |
| | |
| | 17.)FBC 1918.3, GABLES SHALL BE |
| | STRUCTURALLY CONTINUOUS BETWEEN POINTS |
| | OF LATERAL SUPPORT.SHOW HOW THIS WILL |
| | BE ACHIEVED.PROVIDE GABLE END DETAIL, |
| | LATERAL BRACING ON THE ROOF TRUSS PLAN. |
| | SECTION 4 SHOULD REFLECT WHAT YOU ARE |
| | BUILDING; IT IS CONFUSING.CLARIFY AND |
| | SHOW THE T&G ON THE ELEVATIONS. |
| | |
| | 18.)PROVIDE DOOR, GARAGE DOOR, AND |
| | WINDOW BUCK DETAILS.COMPLY WITH FBC |
| | 1707.4.4.2. |
| | |
| | 19.)PROVIDE TWO COPIES OF PRODUCT |
| | APPROVALS FOR: |
| | IMPACT SINGLE HUNG WINDOW |
| | IMPACT CASEMENT WINDOW |
| | MULLIONS |
| | IMPACT FRENCH DOORS |
| | IMPACT SIDELITES FOR FRENCH DOORS |
| | ROOF TILE |
| | GARAGE DOOR (PLAN SHOWS 8' ALMARR |
| | MODEL 950) |