| Plan Review Notes For Permit 03040918 |
| Permit Number |
03040918 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-05-05 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1-RESUBMIT STORM SHUTTERS INFORMATION | | | WITH UPDATED SBCCI PRODUCT APPROVAL | | | THAT MATCHES ENGINEERED DRAWINGS. | | | 2-REVISE DETAIL S-21 FOR COLUMN BETWEEN | | | GARAGE AND STAIRWAY TO MATCH CONDITION | | | SHOWN ON 2ND FLOOR FRAMING PLAN. SEC. | | | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. | | | 3-ROOF FRAMING PLAN: REVISE CONNECTOR | | | TC-1 FOR FRAMED WALL. NEED WOOD TO | | | WOOD CONNECTOR. SEC. 104.2.1.2 CITY | | | AMENDMENTS TO FBC 2001. | | | 4-WINDOW 34SH DOESN'T PROVIDE THE 24" | | | CLEAR HEIGHT AS REQUIRED BY SECTION | | | 1005.4 FBC 2001. REVISE AS REQUIRED. |
|