Plan Review Notes
Plan Review Notes For Permit 03040784
Permit Number 03040784
Review Stop M
Sequence Number 3
Notes
Date Text
2004-01-21 00:00:00DENIED:
 1.PLANS ARE NOTE SIGNED, SEALED AND
 DATED BY THE ENGINEER OF RECORD AS
 REQUIRED PER FS 471.025.
  
 2.PLANS ORIGINALLY SUBMITTED WERE FOR
 A MAINTENANCE BUILDING WITH EXHAUST &
 MAKE UP AIR.REVISION SUBMITTED OMMITED
 EXHAUST AND NOW INDICATES A WALL UNIT.
 MAINTENANCE OR GARAGES SHALL NOT HAVE
 COMFORT COOLING ONLY UNITS USED FOR
 DEHUMIDIFICATION THAT ARE CONTROLLED BY
 A HUMIDISTAT NOT A THERMOSTAT.
  
 3.PROVIDE OUTSIDE AIR CALCULATIONS
 AND A SUMMARY AS TO WHAT TYPE OF
 MAINTENANCE IS TO BE DONE.INDICATE IF
 EQUIPMENT WITH COMBUSTION ENGINES WILL
 BE STORED OR REPAIRED IN THIS AREA.
  
 4.PROVIDE OUTSIDE AIR CALCUALTIONS FOR
 THE LAUNDRY ROOM PER 2001 FBC(M) 403.3.
  
 5.INDICATE TYPE OF DRYERS COMMERCIAL
 OR DOMESTIC.PLEASE NOTE, INSTALLATIONS
 EXHAUSTING GREATER THAN 200 CFM, SHALL
 BE PROVIDED WITH MAKE-UP AIR.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.