| Plan Review Notes For Permit 03040784 |
| Permit Number |
03040784 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2004-01-21 00:00:00 | DENIED: | | | 1.PLANS ARE NOTE SIGNED, SEALED AND | | | DATED BY THE ENGINEER OF RECORD AS | | | REQUIRED PER FS 471.025. | | | | | | 2.PLANS ORIGINALLY SUBMITTED WERE FOR | | | A MAINTENANCE BUILDING WITH EXHAUST & | | | MAKE UP AIR.REVISION SUBMITTED OMMITED | | | EXHAUST AND NOW INDICATES A WALL UNIT. | | | MAINTENANCE OR GARAGES SHALL NOT HAVE | | | COMFORT COOLING ONLY UNITS USED FOR | | | DEHUMIDIFICATION THAT ARE CONTROLLED BY | | | A HUMIDISTAT NOT A THERMOSTAT. | | | | | | 3.PROVIDE OUTSIDE AIR CALCULATIONS | | | AND A SUMMARY AS TO WHAT TYPE OF | | | MAINTENANCE IS TO BE DONE.INDICATE IF | | | EQUIPMENT WITH COMBUSTION ENGINES WILL | | | BE STORED OR REPAIRED IN THIS AREA. | | | | | | 4.PROVIDE OUTSIDE AIR CALCUALTIONS FOR | | | THE LAUNDRY ROOM PER 2001 FBC(M) 403.3. | | | | | | 5.INDICATE TYPE OF DRYERS COMMERCIAL | | | OR DOMESTIC.PLEASE NOTE, INSTALLATIONS | | | EXHAUSTING GREATER THAN 200 CFM, SHALL | | | BE PROVIDED WITH MAKE-UP AIR. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|