| Plan Review Notes For Permit 03040784 |
| Permit Number |
03040784 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-04-23 00:00:00 | ***** NOTE REDLINED **** | | | | | | FEEDER SHOWN AS 3-#3/6`S? | | | SHOULD BE 3/0`S PER 310-16. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|