| Plan Review Notes For Permit 03040756 |
| Permit Number |
03040756 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-09-04 00:00:00 | APPROVED PROVISO: | | | | | | 1) ELECTRONIC SWITCHES ARE REQUIRED | | | ON THE BACKFLOW DEVICE FOR FIRE | | | SERVICE. | | | | | | 2) WET FIRE HYDRANTS ARE REQUIRED | | | PRIOR TO, DURING AND AFTER | | | CONSTRUCTION. | | | | | | 3) TEMPORARY STANDPIPES ARE REQUIRED | | | WHEN THE BUILDING IS THREE STORIES | | | OR THIRTY FEET IN HEIGHT. | | | | | | 4) THE FIRE ALARM SYSTEMS SHALL BE UL | | | LISTED FOR CENTRAL STATION SERVICE | | | SINCE PERMITS WILL BE RECEIVED AFTER | | | THE AUGUST 1, 2003 EFFECTIVE DATE. | | | | | | 5) NFPA 13R SYSTEMS ARE NOT ALLOWED | | | FOR 5 STORY BUILDINGS. | | | | | | 6) WAFER CHECK VALVES ON THE SUPPLY | | | SIDE OF A FIRE PUMP CANNOT BE INSTALLED | | | SO CLOSE TO THE PUMP. | | | | | | 7) FINAL EASEMENTS WITH REGARDS TO | | | FIRE LINES AND UTILITIES HAVE NOT | | | YET BEEN WORKED OUT. ALL APPROVALS | | | MUST BE OBTAINED FROM THE PROPER | | | AUTHORITIES. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|