| Plan Review Notes For Permit 03040756 |
| Permit Number |
03040756 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-06-24 00:00:00 | ************** UNSAT *********** | | | | | | 1)NOTE: PLEASE SEE THAT THERE ARE STILL | | | SOMERECEPTS MISSING FOR 2' OF WALL | | | SPACE.210-52 | | | | | | 2)NOTE: PLANS/RISER SHOW 3 PARALLEL RUNS | | | OF UNGROUNDED CONDUCTORS, HOWEVER ONLY | | | SHOWS TWO PARALLEL RUNS OF GROUNDED | | | CONDUCTORS? DUE TO INDUCTIONAND INDUCT- | | | -IVE HEATING, A 3RD RUN OF THE GROUNDED | | | (NEUTRAL) CONDUCTOR WILL BE REQ`D. | | | 300-20/310-4 | | | THIS WOULD NOT BE REQ`D FOR BLDG 1, SERV | | | -#4. | | | | | | 3)NOTE: PLEASE SEE 250-24, NOTE ON RISER | | | DIAGRAM FOR CLUBHOUSE MENTIONS, TO BOND | | | GROUND AND NEUTRAL TOGETHER, THIS DONE | | | AT THE FIRST MEANS OF DISC, AS PER | | | 250-24 | | | | | | 4)NOTE: PLEASE SEE THAT THERE IS NOT | | | ENOUGH INFORMATION FOR FIRE PUMP, | | | FIRE PUMP VOLTAGE, MEANS OF DISC, CODE | | | LETTER, SIZING OF DISC MEANS FOR LOCKED | | | ROTOR, RISER DIAGRAM ETC.430-150,430-151 | | | (B), 695-4B-1,2 ETC. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | PLEASE SEE OTHER REVIEWS, THAT MAY HAVE | | | AN AFFECT ON ELECTRICAL PLANS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|