| 2003-04-30 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 11 |
| | FHA-AMEND 98 DESIGN MANUAL |
| | |
| | 1) SHTS A5.05 & A5.06 LAVS SHALL BE 34" |
| | MAX FROM FLOOR TO FLOOD RIM LEVEL. SEE |
| | DETAIL PAGE 7.52 DESIGN MANUAL. |
| | 2) SHT A5.02 - 11-4.16.5 FLUSH CONTROLS |
| | SHALL BE MOUNTED ON THE WIDE SIDE OF |
| | TOILET AREAS. (AWAY FROM SIDE GRAB BARS) |
| | 3) SEPARATE POOL PERMIT REQUIRED. HEALTH |
| | DEPT. PLAN REVIEW REQUIRED FOR FACILIT- |
| | IES. |
| | 3) SEPARATE IRRIGATION PERMIT REQUIRED. |
| | 4) SHT P14.03 CLEANOUTS REQUIRED IN BOTH |
| | BREEZEWAYS. SECTION 708.3.1 (MAX 100') |
| | 5) ALL UNITS - PLEASE SPECIFY EITHER |
| | SPECIFICATION "A" OR "B" BATHROOMS AS |
| | REQUIRED BY DESIGN MANUAL REQUIREMENT |
| | 7B, PAGE 7.35. |
| | 6) SHT P14.07 WATER RISER DIAGRAMS, THE |
| | WATER HAMMER ARRESTORS REQUIRED IN SEC. |
| | 604.9, (ICE MAKER, DISHWASHER, WASH |
| | MACHINE), SHALL BE LOCATED NEAR THE FIX- |
| | TURE IN AN "EFFECTIVE RANGE" NOT IN THE |
| | CEILING AS SHOWN. PDI-WH 201 AND MANUF. |
| | INSTALLATION INSTRUCTIONS. |
| | 7) SHT P14.06 RISERS S4 & S5, THE WASTE |
| | STACK SHALL BE THE SAME SIZE THROUGHOUT |
| | THE LENGTH OF THE WASTE STACK. SECTION |
| | 910.4 |
| | 8) RPZ BACKFLOW REQUIRED IN WATER SERV. |
| | AT EACH BLDG. |
| | |