| Date |
Text |
| 2003-04-29 00:00:00 | *********** UNSAT ***************** |
| | |
| | 1)NOTE: PLEASE CLARIFY DISTANCE FOR |
| | VOLTAGE DROP ON SITE LIGHTING. |
| | WE ARE UNDER 2002FBC. PLEASE SEE WIND |
| | LOAD REQ`D FOR POLES. NOTES 120MPH. |
| | |
| | 2)NOTE: PLEASE PLACE NOTE/REQUIREMENTS |
| | ON PLAN FOR FHAC 24 CFR 100.205. |
| | |
| | 3)NOTE: PLEASE SEE PLANS FOR RECEPT |
| | SPACING. SOME MISSING PER 210-52. |
| | 2' OF WALL SPACE. |
| | |
| | 4)NOTE: PLEASE NOTE, SD`S ARE TO BE A |
| | MIN OF 3' FROM BATH DOOR AND KITCHEN. |
| | |
| | 5)NOTE: PLEASE CLARIFY ALL SERVICE |
| | ENTRANCE CONDUCTORS SIZE AND # OF PARA- |
| | -LLEL RUNS. PLEASE SEE 240-3 B&C |
| | 110-14 AND 310-16 |
| | |
| | 6)NOTE: PLEASE CLARIFY WATER HEATER LOAD |
| | SHOWN AT 11800W? |
| | PLEASE CORRELATE W/ PANEL SCHEDULE. |
| | SHOWN BEING DIFFERENT. |
| | |
| | 7)NOTE: PLEASE SEE E-16.09 NOTE AT |
| | BOTTOM OF PANELS MENTIONS : SEE EXX FOR |
| | LOADS. PLEAS FILL IN APPROPRIATE PAGE. |
| | |
| | 8)NOTE: PLEASE SEE LIST/CLARIFY THE |
| | REQ`D ARC FAULT PROTECTED CIRCUITS PER |
| | 210-12 |
| | |
| | 9)NOTE: PLEASE PANEL C2, SHOWS LOCATION |
| | TO BE IN UTILITY ROOM. PLEASE SEE FLOOR |
| | PLAN, SHOWN IN HALL? PLEASE CORRELATE. |
| | |
| | 10)NOTE: PLEASE CORRELATE LOAD SHOWN FOR |
| | WASHER. PANEL SHOWS AS 1.0KW AND LOAD |
| | CALCS SHOWS AS 1.5KW(REQ`D) 220-16B |
| | |
| | 11)NOTE: PLEASE SEE MAIN GROUNDING |
| | ELECTRODE REQ`D TO FOOTER STEEL 250-50/ |
| | SIZED PER 250-66 SHOWN AS #4/#6 AND #2 |
| | FOR ALL OTHERS AND BONDING? |
| | |
| | 12)NOTE: PLEASE CLARIFY MAINS SHOWN AS |
| | "SHUNT TRIP". PLEASE CLARIFY IF THERE |
| | IS STILL A MANUAL MEANS OF DISCAND |
| | RATED FOR SERVICE. 230-76-230-79 |
| | PLEASE NOTE, SHUNT TRIPS ARE NOT RATED |
| | FOR MEANS OF DISC. |
| | |
| | 13)NOTE: PLEASE NOTE, PLANS AND RISER |
| | MENTIONS ALUM CONDUCTORS FOR GROUNDING |
| | AND BONDING. PLEASE NOTE, PER LOCAL |
| | AMENDMENTS TO FBC/NEC AS ADOPTED BY THE |
| | CITY OF WEST PALM BEACH, ART 250-62/ |
| | 310-2. |
| | PLEASE ALSO ADJUST EQUIPMENT GROUNDING |
| | TO APT UNITS. PLEASE NOTE, MIXING OF |
| | CONDUCTOR AND OR DISSIMILAR METALS. |
| | |
| | 14)NOTE: PLEASE SEE APPLICATION, MENTION |
| | -S CLUBHOUSE UNDER THIS #. PLEASE NOTE, |
| | WILL BE SEPARATED UNDER SEPARATE PERMIT |
| | AND IS ONLY REVIEW UNDER THIS PERMIT # |
| | AT THIS TIME. |
| | |
| | 15)NOTE: PLEASE CLARIFY AND PROVIDE |
| | MORE INFORMATION ON FIRE PUMP SHOWN IN |
| | CLUBHOUSE? A COMPLETE REVIEW CAN NOT BE |
| | DONE AT THIS TIME FOR THIS.SPECS ETC |
| | |
| | 16)NOTE: PLEASE SEE LOCATION OF PANEL |
| | "LPA" SHOWN IN LIBARY. PLEASE CHANGE |
| | LOCATION DUE TO PROXIMITY OF EASILY |
| | IGNITABLE MATERIALS.384-7 |
| | |
| | 17)NOTE: PLEASE PROVIDE GROUNDING |
| | ELECTRODE CONDUCTOR SIZES FOR CLUBHOUSE, |
| | NOTES MENTIONS SEE RISER, RISER SAYS |
| | SEE GROUNDING DETAIL? PLEASE SHOW AND |
| | CORRELATE. |
| | |
| | PLEASE NOTE: THERE MAY BE FURTHER |
| | COMMENTS DUE TO SOME ITEMS NOT BEING |
| | COMPLETE AT THIS TIME. |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | PLEASE ALSO SEE FIRE REVIEW COMMENTS |
| | THAT MAY AFFECT ELECTRICAL PLANS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |