| 2004-04-30 00:00:00 | 1) THE ENTRY SIGN LOCATED NEAR THE | | | OPENING SHALL BE IN ADDITION TO THE | | | SIGN REQUIRED ON EXECUTIVE CENTER | | | DRIVE TO DIRECT EMERGENCY SERVICES TO | | | THE TWO APARTMENT BUILDINGS LOCATED | | | BEHIND THE EXISTING CLEAR LAKE | | | COLONY. | | | | | | 2) END OF LINE DEVICES SHOWN ON FIRE | | | ALARM SYSTEM WIRING. THE FIRE ALARM | | | SYSTEMS SHALL BE CLASS A, STYLE D, OR | | | FULLY ADDRESSABLE. | | | | | | 3) NFPA 13R IS REFERENCED ON PLANS. | | | NFPA 13R SYSTEMS ARE FOR RESIDENTIAL | | | BUILDINGS OF FOUR OR LESS STORIES. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|