| Plan Review Notes For Permit 03040755 |
| Permit Number |
03040755 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-06-24 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | 1) FROM PREVIOUS REVIEW. CLEANOUTS RE- | | | QUIRED IN BOTH BREEZWAYS, (STAIRWAYS), | | | SHTS P14.01 & P14.03. CLEANOUTS SHALL BE | | | FLOOR CLEANOUTS AS THEY ARE REQUIRED TO | | | BE TWO WAY CLEANOUTS, OR MORE CLEANOUTS | | | WILL BE REQUIRED AT THE UPSTREAM END OF | | | THE BLDG DRAIN. 708.5. CLEANOUTS ARE | | | REQUIRED TO BE ACCESSIBLE SO THEY SHALL | | | BE LOCATED OUTSIDE OF THE UNITS. 708.10 | | | 2) SHT P14.07 WATER RISER DIAGRAMS. IF | | | WATER HAMMER ARRESTORS ARE INSTALLED AT | | | THE WATER HEATERS THEY SHALL BE LOCATED | | | AS REQUIRED FOR ALL OTHER WATER HAMMER | | | ARRESTORS. PDI-WH 201 & MANUF. INSTALL. | | | INSTRUCTIONS. | | | 3) SUBMIT A HORIZONTAL SANITARY RISER | | | DIAGRAM. SHOW ALL RISER TIE-INS AND | | | SHOW DRAINAGE FIXTURE UNITS AS THEY | | | ACCUMULATE IN THE SYSTEM. 104.2.1 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 |
|