| Notes |
| Date |
Text |
| 2003-04-30 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | FHA-AMEND 98 DESIGN MANUAL | | | | | | 1) SHTS A5.05 & A5.06 LAVS SHALL BE 34" | | | MAX FROM FLOOR TO FLOOD RIM LEVEL. SEE | | | DETAIL PAGE 7.52 DESIGN MANUAL. | | | 2) ALL UNITS - PLEASE SPECIFY EITHER | | | SPECIFICATION "A" OR "B" BATHROOMS AS | | | REQUIRED BY DESIGN MANUAL REQUIREMENT | | | 7B PAGE 7.35 | | | 3) SEPARATE PERMIT REQUIRED FOR IRRIGA- | | | TION. | | | 4) SHT P14.01 CLEANOUTS REQUIRED IN BOTH | | | BREEZEWAYS. SECTION 708.3.1 (MAX. 100') | | | 5) SHT P14.06 RISERS S4 & S5, THE WASTE | | | STACH SHALL BE THE SAME SIZE THROUTHOUT | | | THE LENGTH OF THE WASTE STACK. SECTION | | | 910.4. | | | 6) SHT P14.07 WATER RISER DIAGRAMS, THE | | | WATER HAMMER ARRESTORS REQUIRED IN SECT. | | | 604.9, (ICE MAKER, DISHWASHER. WASH | | | MACHINE), SHALL BE LOCATED NEAR THE FIX- | | | TURES IN AN "EFFECTIVE RANGE" NOT IN THE | | | CEILING AS SHOWN. PDI-WH 201 & MANUF. | | | INSTALLATION INSTRUCTIONS. | | | 7) RPZ BACKFLOW REQUIRED FOR WATER | | | SERVICE AT EACH BLDG. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 | | | (561) 805-6721 | | | FAX (561) 653-2692 |
|