| 2003-05-05 00:00:00 | DENIED: |
| | APPARTMENTS |
| | |
| | 1.PLANS SHEET A15.01 ELEC METER RM, |
| | AS PER 2001 FBC(M) 401.5.2, EXHAUST |
| | OPENINGS SHALL BE LOCATED AS NOT TO |
| | CREATE A NUISANCE.EXHAUST AIR SHALL |
| | NOT BE DIRECTED ONTO WALKWAYS. |
| | |
| | 2.PLEASE INDICATE THE USE OF THE ROOMS |
| | WHERE AHU-EL IS LOCATED. |
| | |
| | 3.CLARIFY EXTERIOR WALL - PLAN SHEET |
| | M15.03, INDICATES AN EXHAUST TERMINATION |
| | WITH A FIRE DAMPER.PLAN SHEET A1.04 |
| | EXTERIOR WALL W1 INDICATES 1 HR, NO FIRE |
| | DAMPERS INDICATED ON O.A. INTAKES. |
| | |
| | 4.PLAN SHEET M15.06 DETAIL OF THE |
| | CONDENSATE TRAP CLARIFY VENT CAP IN OPEN |
| | PLENUM. |
| | |
| | 5.PROVIDE OUTSIDE AIR CALCS AS PER |
| | 2001 FBC(M) TABLE 403.3 |
| | |
| | CLUBHOUSE: |
| | 1.PLAN SHEET CH M15.01 DRYER EXHAUST |
| | PENETRATING RATED WALL AT FIRE PUMP RM, |
| | THE IS NOT ACCEPTABLE.FIRE DAMPERS |
| | CANNOT BE INSTALLED IN DRYER DUCT DUE |
| | TO LINT BUILD-UP. |
| | |
| | 2.INDICATE WHAT TYPE OF DRYERS ARE TO |
| | BE INSTALLED IN THE PUBLIC LAUNDRY ROOM. |
| | (COMMERCIAL?) |
| | |
| | 3.PLEASE NOTE, SHOULD DRYERS IN THE |
| | LAUNDRY ROOM EXHAUST GREATER THAN |
| | 2,000 CFM, AIR MAKE UP IS REQUIRED. |
| | |
| | 4.PROVIDE OUTSIDE AIR CALCS AS PER |
| | TABLE 403.3. |
| | |
| | 5.PLEASE CLARIFY THE MOP SINK IN THE |
| | AHU CLOSET. |
| | |