| Plan Review Notes For Permit 03040754 |
| Permit Number |
03040754 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2003-11-17 00:00:00 | DENIED | | | ~~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE MAKE THE FOLLOWING CHANGES TO | | | THE PLANS FOR CODE COMPLIANCE. | | | | | | 1} THE #4 KEYNOTE ON SHEET E16.10 | | | INDICATES A #4 ALUMINUM GROUND.ARTICLE | | | 310.2(B)(2),WEST PALM BEACH AMMENDMENTS | | | PROHIBITS THE USE OF ALUMINUM FOR | | | GROUNDING. | | | | | | 2} PLEASE INDICATE THE FEEDER SIZES ON | | | SHEET E16.10. | | | | | | 3} SMOKE DETECTORS AND FANS IN BEDROOMS | | | MUST BE ON AN ARC FAULT PROTECTED | | | CIRCUIT. SEE 212.12(B).ALSO PLEASE LOOK | | | AT THE DEFINITION OF "OUTLET" IN THE | | | NEC IF THERE ARE QUESTIONS TO THIS | | | REFERENCE. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718. |
|