| Date |
Text |
| 2003-07-01 00:00:00 | 1) CLUBHOUSE FIRE PUMP ROOM MISSING | | | REQUIRED EMERGENCY LIGHTING. | | | | | | 2) LETTER NEEDS TO BE NOTORIZED THAT | | | WAS SIGNED BY FRANCISCO ROJO. | | | | | | 3) EMERGENCY LIGHTS SEEM CONFUSING. | | | PLEASE INDICATE ALL EMERGENCY LIGHTS | | | IN CORRIDORS AND STAIRWELLS. | | | | | | 4) SIAMESE CONNECTION APPEARS TO FACE | | | THE WRONG DIRECTION. HOSE WILL KINK | | | WHEN CONNECTED TO BUILDING 1. | | | | | | 5) ON JUNE 30, 2003, WRITER MET WITH | | | ALEX BARROSO AT FIRE STATION # 4. IT | | | WAS EXPLAINED THAT ANOTHER FIRE HYDRANT | | | IS NEEDED IMMEDIATELY UPON ENTERING THE | | | NEW APARTMENT COMPLEX. | | | | | | WE ALSO DISCUSSED THAT SINCE YOU | | | CANNOT SEE THE NEW BUILDINGS FROM | | | EXECUTIVE CENTER DRIVE AND THAT YOU | | | MUST ENTER VIA LAKE PLACE THEN | | | PROPER SIGNAGE WILL BE REQUIRED ON | | | THE ROADWAY. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|