Plan Review Notes
Plan Review Notes For Permit 03040754
Permit Number 03040754
Review Stop ENG
Sequence Number 1
Notes
Date Text
2003-04-16 00:00:00FAILED:
 1. PLEASE NOTE THAT A SEPARATE PERMIT
 APPLICATION AND FEES FOR UNDERGROUND
 UTILITIES AND SITE WORK WILL BE REQUIRED
 2. A DDCV FOR ALL PRIVATE FIRE HYDRANT
 WILL BE REQUIRED.
 3. A SEPARATE BACKFLOW PREVENTER FOR
 EACH BUILDING IN DOMESTIC WATER LINE
 AND ONE FOR THE PROPOSED POOL IS
 REQUIRED.
 4. METER BANK 10-5/8" METERS AS PROPOSED
 MUST BE APPROVED BY PUBLIC UTILITIES
 659-8040.
 5. PLEASE SUBMIT TWO SETS OF CIVIL PLANS
 TO PUBLIC UTILITIES FOR THEIR REVIEW
 AND APPROVAL PRIOR TO SUBMITTING TO THE
 BUILDING DEPARTMENT.
 6. DUMPSTER ENCLOSURE MUST BE SIZED PER
 CITY REQUIREMENTS IF TO BE PICKED UP BY
 THE CITY.
 7. ANY WORK WITHIN PUBLIC ROW WILL
 REQUIRES PERMIT FROMCITY ENGINEER
 OFFICE, 659-8040.
 8. POLLUTION/EROSION PLAN MUST BE ADDED
 TO THE PLANS, PLAN MUST BE INSTALLED IN
 FIELD PRIOR TO ANY EARTH/ CONSTRUCTION
 WORK AND MUST BE IN WORKING CONDITION
 THROUGHOUT THE CONSTRUCTION DURATION.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI