Plan Review Notes
Plan Review Notes For Permit 03040753
Permit Number 03040753
Review Stop M
Sequence Number 1
Notes
Date Text
2003-05-03 00:00:00 
 NO MECHANICAL PLANS SUBMITTED FOR REVIEW
  
 PROVIDE PLANS INDICATING ANY CHANGES TO
 THE EXISTING HVAC SYSTEM.
  
 PROVIDE REVISED OUTSIDE AIR CALCS AS PER
 2001 FBC(M) TABLE 403.3.
  
 INDICATE IF ANY MODIFICATION TO HOOD
 OR SUPPRESSION SYSTEM IS PLANNED.SHOW
 ANY NEW WORK TO BE DONE.PLEASE NOTE,
 SEPARATE PERMITS REQUIRED FOR HOOD, FIRE
 SUPPRESSION, OR WALK-IN COOLERS/FREEZERS
 PROVIDE PLANS & MANUFACTURERS SUBMITTAL
 DATA WITH PERMIT APPLICATIONS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.