Plan Review Notes
Plan Review Notes For Permit 03040745
Permit Number 03040745
Review Stop B
Sequence Number 2
Notes
Date Text
2003-06-20 00:00:00THE AHRENS/UPHOFF PLAN SHEET 401 GRID
 LINES DO NOT AGREE THE XUAN CHENG PAGE
 TITLED "FOOTING PLAN" AND NEITHER OF
 THOSE MATCH THE USA "ANCHOR BOLTPLAN.
  
 THE CHEN PLAN SHOWS FOUR COLUMNS AT
 LINE4, THE USA AND UPHOFF PLANS THREE.
  
 WHO WILL BE ENGINEER OF RECORD?
 ARCHITECT UPHOFF OR XUAN
 CHEN, PE?PLEASE PROVIDE DESIGN
 RESPONSIBILITY IN ACCORDANCE WITH FAC
 61G15-31.
  
 THE CALCULATIONS BY USA DATED 6/4/03 DO
 NOT INVESTIGATE THE ROOF AND WALL
 SHEETING AND THEIR CONNECTIONS.
  
 THE XUAN CHEN CALCULATIONS HAVE A USA
 DESIGN DATA PAGE 4-64, THAT CITES THE
 1986 MBMA CODE FOR WIND DESIGN WHICH IS
 NOT ACCEPTABLE FOR THE 2001 FBC.