| Plan Review Notes For Permit 03040745 |
| Permit Number |
03040745 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-06-20 00:00:00 | THE AHRENS/UPHOFF PLAN SHEET 401 GRID | | | LINES DO NOT AGREE THE XUAN CHENG PAGE | | | TITLED "FOOTING PLAN" AND NEITHER OF | | | THOSE MATCH THE USA "ANCHOR BOLTPLAN. | | | | | | THE CHEN PLAN SHOWS FOUR COLUMNS AT | | | LINE4, THE USA AND UPHOFF PLANS THREE. | | | | | | WHO WILL BE ENGINEER OF RECORD? | | | ARCHITECT UPHOFF OR XUAN | | | CHEN, PE?PLEASE PROVIDE DESIGN | | | RESPONSIBILITY IN ACCORDANCE WITH FAC | | | 61G15-31. | | | | | | THE CALCULATIONS BY USA DATED 6/4/03 DO | | | NOT INVESTIGATE THE ROOF AND WALL | | | SHEETING AND THEIR CONNECTIONS. | | | | | | THE XUAN CHEN CALCULATIONS HAVE A USA | | | DESIGN DATA PAGE 4-64, THAT CITES THE | | | 1986 MBMA CODE FOR WIND DESIGN WHICH IS | | | NOT ACCEPTABLE FOR THE 2001 FBC. |
|