2003-04-26 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 ADMIN. CODE, CHAPTER
 ONE & AMENDS.
  
 1) SHT 101 WATER SERVICE, PVC SHALL NOT
 BE USED PER TABLE 605.5
 2) SHT 301 MINIMUM FACILITIES, PER TABLE
 403.1 A W/C, LAV, DRINKING FOUNTAIN, AND
 A SERVICE SINK ARE REQUIRED.
 3) SHT 501 PLEASE CONTACT RODNEY COMPO,
 ENVIRONMENTAL COMPLIANCE, INDUSTRIAL
 PRETREATMENT FOR SIZE OF SAND INTERCEP-
 TOR. WASTE ORD. #2938-96. (561) 837-4074
 4) SHT 501 PER 104.3.1.1 A SANITARY
 RISER DIAGRAM IS REQUIRED.
 5) SHT 501 THE 3" VENT SHALL CONNECT
 ABOVE THE CENTER LINE OF THE HORIZONTAL
 DRAIN PIPE. SECTION 905.3
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692