| Plan Review Notes For Permit 03040745 |
| Permit Number |
03040745 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-04-26 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 ADMIN. CODE, CHAPTER | | | ONE & AMENDS. | | | | | | 1) SHT 101 WATER SERVICE, PVC SHALL NOT | | | BE USED PER TABLE 605.5 | | | 2) SHT 301 MINIMUM FACILITIES, PER TABLE | | | 403.1 A W/C, LAV, DRINKING FOUNTAIN, AND | | | A SERVICE SINK ARE REQUIRED. | | | 3) SHT 501 PLEASE CONTACT RODNEY COMPO, | | | ENVIRONMENTAL COMPLIANCE, INDUSTRIAL | | | PRETREATMENT FOR SIZE OF SAND INTERCEP- | | | TOR. WASTE ORD. #2938-96. (561) 837-4074 | | | 4) SHT 501 PER 104.3.1.1 A SANITARY | | | RISER DIAGRAM IS REQUIRED. | | | 5) SHT 501 THE 3" VENT SHALL CONNECT | | | ABOVE THE CENTER LINE OF THE HORIZONTAL | | | DRAIN PIPE. SECTION 905.3 | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 | | | (561) 805-6721 | | | FAX (561) 653-2692 |
|