Plan Review Notes
Plan Review Notes For Permit 03040745
Permit Number 03040745
Review Stop E
Sequence Number 1
Notes
Date Text
2003-04-23 00:00:00*************** UNSAT *************
  
 1)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125%. 215-3/230-42
  
 2)NOTE: PLEASE SEE 225-31 FOR MEANS OF
 DISCONNECTING FEEDERS COMING TO NEW
 DETACHED BLDG.
  
 3)NOTE: PLEASE SHOW LOAD ON EXISTING
 PANEL THAT NEW FEED IS COMING FROM , TO
 INCLUDE NEW LOAD.215-5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]