Plan Review Notes
Plan Review Notes For Permit 03040745
Permit Number 03040745
Review Stop B
Sequence Number 1
Notes
Date Text
2003-04-24 00:00:00THE FOUNDATION PLAN ON SHEET 401 OF THE
 AHREN'S PLANS DOES NOT AGREE WITH THE
 ANCHOR BOLT PLACEMENT PLAN ON THEUSA
 SHEET F1 OF 2.HAS THE ARCHITECT
 REVIEWED THE USA PLAN?
  
 PROVIDE A CONSTRUCTION DETAIL FOR THE
 ANCHOR BOLT PLATES TO BE LOCATED ON THE
 6' HIGH MASONRY WALL.
  
 PROVIDE COMPLETE STRUCTURAL
 CALCULATIONS FOR THE FOUNDATION AND
 MASONRY WALL SYSTEM. FBC 104.2
  
 PROVIDE THE SPECIFICATIONFOR THE
 REINFORCED MASONRY.SEE FBC 2103.1.
  
 THE USA CALCULATIONS DECLARE ALLOWABLE
 DEFLECTIONS TO USA/MBMA STANDARDS. THE
 CALCULATIONS MUST ALSO COMPLY WITH FBC
 1610.
  
 SEE ALSO FBC 1609 AND ALLOWABLE LOAD
 REDUCTIONS.