| Plan Review Notes For Permit 03040662 |
| Permit Number |
03040662 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-05-15 00:00:00 | REF: NFPA 101 LIFE SAFETY 2000 EDITION | | | CH.40 & CH.7 | | | | | | 1) PLEASE PROVIDE LOCATION OF STORED OIL | | | DRUMS IN WAREHOUSE. | | | | | | 2) THERE APPEARS TO BE AN EXIT SIGN OVER | | | THE DOOR OF WAREHOUSE RESTROOM. | | | | | | 3) PLEASE PROVIDE INTERIOR WALL AND | | | CEILING FINISH CLASSIFICATION. | | | | | | 4) SEPARATE PERMIT APPLICATIONS AND FEES | | | FOR FIRE SPRINKLER AND FIRE ALARM SYSTEM | | | WILL BE REQUIRED. | | | | | | NATE MCCRAY, CAPTAIN | | | 659-8096, EXT 8497 | | | 805-6722 OR 835-2910 |
|