Plan Review Notes
Plan Review Notes For Permit 03040662
Permit Number 03040662
Review Stop E
Sequence Number 1
Notes
Date Text
2003-04-24 00:00:00************** UNSAT **************
  
 1)NOTE: PLEASE CLARIFY LOCATION FOR
 STORAGE AND USE OF OIL IN DRUMS AND/OR
 ANY HAZARDOUS LOCATION PER NEC ART 500.
  
  
 2)NOTE: PLEASE SHOW REQ`D SIGN CIRCUIT
 PER 600-5.
  
 3)NOTE: PLEASE PROVIDE "SHOW" WINDOW"
 RECEPTS PER 210-62
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]