| Plan Review Notes For Permit 03040660 |
| Permit Number |
03040660 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-05-08 00:00:00 | 1) PLEASE EXPLAIN HOW THE TWO EXITS | | | WITHIN WAREHOUSE 019 ARE REMOTELY | | | LOCATED. IT APPEARS THAT A SINGLE | | | FIRE INCIDENT COULD BLOCK BOTH | | | EXITS. | | | | | | 2) FIRE ALARM NOTES INDICATE CLASS B, | | | STYLE C CIRCUITS. ONLY CLASS A, STYLE | | | D, CIRCUITS ARE ALLOWED. | | | | | | 3) PROVIDE SEPARATE PLANS AND PERMITS | | | FOR FIRE ALARM EQUIPMENT. | | | | | | 4) PROVIDE SEPARATE PLANS AND PERMITS | | | FOR FIRE SPRINKLER REMODEL. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|