Notes
Date Text
2003-04-15 00:00:00CALLED (503) 703-0322, PIPING IS OKAY,
 SEE BUILDING PERMIT 01121500 FOR
 VENTILATION IN THE ENGINE ROOM - FANS
 RUN CONTINUOUSLY, SENSORS ARE TO BE
 INSTALLED AS PER PLAN SHEET M-4.2.
  
 PROVISO:ENGINE ROOM TO COMPLY WITH
 1997 SMC CHAPTER 11.PLANS DO NOT
 INDICATE A BREATHING APPARATUS AS
 DICTATED IN SECTION 1105.8.TERMINATION
 OF RELIEF DEVICES SHALL BE OUTSIDE OF
 STRUCTURE NOT LESS THAN 15 FT ABOVE THE
 ADJOINING GROUND AND NOT LESS THAN 20 FT
 FROM ANY WINDOW, VENTILATION OPENING OR
 EXIT TO ANY BUILDING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.