| 2003-04-18 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | TO THE PLAN FOR CODE COMPLIANCE. | | | | | | 1} THE GROUNDING ELECTRODE CONDUCTOR FOR | | | A 400 AMP SERVICE MUST COMPLY WITH | | | 250-66.(1/0). | | | | | | 2} THE FEEDERS FOR PANEL "B" MUST | | | CONTAIN AN EQUIPMENT GROUND. | | | | | | 3} THE LAUNDRY CIRCUIT ON THE PANEL | | | SCHEDULE MUST COMPLY WITH | | | 220-16(B).1.5KW. | | | | | | 4} PLEASE LIST THE REQ'D BATH(S) | | | CIRCUIT(S). PER 210-11-C-3 | | | MUST BE 20A AND #12AWG. | | | | | | 5} SMOKE DETECTOR IN THE KITCHEN IS IN | | | VIOLATION OF 8-4.1.2 NFPA-72,CHANGE TO A | | | LISTED HEAT DETECTOR,OR REMOVE. | | | | | | 6} THE SMOKE DETECTOR IN THE ENTRY TO | | | THE MASTER SUITE SHOULD BE LOCATED IN | | | THE VESTIBULE TO MEET THE INTENT OF | | | ARTICLE 8-1.4.1.6.2(2) AS "OUTSIDE" THE | | | SLEEPING AREA. | | | | | | 7} BEDROOM #4 NEEDS A RECEPTACLE TO | | | COMPLY WITH 210-52(A)(1). | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|