2003-04-22 00:00:00************* UNSAT ***********
  
 1)NOTE: PLEASE CORRECT ADDRESS ON PLANS.
 ACTUAL ADDRESS IS 255 EVERNIA. ELECTRIC-
 AL PLANS SEEM TO HAVE CORRECT ADDRESS.
  
 2)NOTE: PLEASE PROVIDE COPY OF CONTRACT
 FOR COMPLETE SCOPE OF WORK, TO INCLUDE
 LABOR AND MATERIALS EVEN IF OWNER SUPPL-
 IED. 104.6.5 CITY-WIDE ADMIN CODE.
 APPL SHOWS 19,450.
  
 3)NOTE: PLEASE CLARIFY AWG AND OCP FOR
 SURGE ARRESTOR ON PANEL. PLEASE ALSO
 SEE MAX # OF #2`S IN 2" CONDUIT. PER
 NEC TABLES.
  
 PLEASE APPLY FOR PERMIT APPLICATION AND
 PAY PERMIT FEES.
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  