| 2003-05-14 00:00:00 | BUILDING DENIED |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) SUBMIT A COPY OF THE PAID RECEIPT FOR |
| | THE COUNTY IMPACT FEES. |
| | |
| | 3) SUBMIT A SOIL BORING TEST REPORT AS |
| | REQUIRED BY CITY AMEND. TO FBC 1804.2.2. |
| | |
| | 4) THE INFORMATION ON THE ENERGY CALCS. |
| | IS INCORRECT. THE CONDITIONED AREA |
| | LISTED ON THE ENERGY CALC. FORM IS |
| | 2292 SQFT AND THE PLAN LISTS 2260 SQFT. |
| | THE OWNER AND BUILDER LISTED ON THE FORM |
| | DOES NOT CORRESPOND TO THE CITY OR |
| | COUNTY RECORDS. PLEASE CORRECT. |
| | |
| | 5) REVISE THE STUCCO SPECIFICATIONS ON |
| | A3 NOTE #7 TO INDICATE THAT 3/8" HIGH |
| | RIB METAL LATH IS REQUIRED TO BE |
| | FASTENED AT EVERY RIB (4"O.C.) AS |
| | REQUIRED BY ASTM C 1063. NOTE #4 AND #5 |
| | ARE THE SAME. |
| | |
| | 6) SPECIFY THE TRUSS CONNECTORS FOR THE |
| | LOWER TRUSSES ON THE 10' HT. WOOD FRAME |
| | BEARING WALL BETWEEN THE ENTRY AND THE |
| | GALLERY ON SHEET S2. |
| | |
| | 7) REVISE THE UPLIFT VALUES OF THE USP |
| | CONNECTORS TO THE VALUES THAT DO NOT |
| | INCLUDE A STRESS INCREASE ON THE STEEL |
| | CALCULATIONS. SEE 2003 USP CATALOG. |
| | |
| | 8) THE OPENING SIZES FOR UNITS #1 AND #2 |
| | ON THE STORM PANEL SCHEDULE ARE REVERSED |
| | FROM THE KEY PLAN. PLEASE CORRECT. |
| | |
| | 9) SUBMIT PRODUCT APPROVALS FOR THE |
| | SINGLE OUTSWING DOOR WITH ONE SIDELITE. |
| | |
| | 10) SUBMIT AN ADDITIONAL COPY OF THE |
| | PRODUCT APPROVAL FOR THE SLIDING GLASS |
| | DOOR. |
| | |
| | 11) SUBMIT AN ADDITIONAL COPY OF THE |
| | SURVEY. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |