| Plan Review Notes For Permit 03040607 |
| Permit Number |
03040607 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-05-07 00:00:00 | BUILDING PROVISO | | | | | | 1) SUBMIT A SOIL BORING TEST REPORT AS | | | REQUIRED BY CITY AMENDMENTS TO FBC | | | 1804.2.2 PRIOR TO POURING FOUNDATION. | | | | | | 2) SUBMIT REVISED UPLIFT VALUES FOR | | | FOR TRUSS CONNECTORS THAT DO NOT INCLUDE | | | THE ONE-THIRD STRESS INCREASE ON THE | | | STEEL CALCULATIONS. SEE FBC 1609.4 AND | | | THE 2003 USP CATALOG. |
|